Flow meter device wholesale manufacturer today: The third case is that, during the commissioning stage of a platform construction, when the liquid level is higher than 3800mm, the radar level meter of the dirty oil tank will frequently jump to 0mm, which leads to the shutdown of the fourth-stage production unit. After on-site inspection, the power supply voltage of the radar level meter transmitter is only 9.5V, which is lower than the working power supply voltage of the radar level meter. By further searching for the cause of the failure, found that when the high liquid level, the voltage at the power supply is 23.7V, the safety gate output drops to 9.7V, judged as a safety gate transmitter failure. After replacing the safety grid, the voltage returns to normal, the cabin radar level meter in the test to rule out the problem. Discover more details at https://www.kaidi86.com/flow-instrument.html.
Measuring principle of radar water level meter: The radar level gauge adopts the working mode of transmitting-reflecting-receiving. The electromagnetic wave emitted by the antenna is reflected by the surface of the measured object and then received by the antenna. After measuring the distance from the water surface to the radar antenna, the elevation of the water surface can be calculated according to the elevation of the radar antenna. The radar water level meter adopts pulse wave technology with low power consumption. It can be powered by two-wire 24 VDC, 485 interface output, or can be directly powered by 12 VDC, SDI-12 interface output, with high accuracy and wider application range.
Level Measurement Considerations: Taking advantage of a specific technology’s ability to reliably address the level measurement in either of these vessels, especially the blowdown flash tank, in a plug-and-play type installation and commissioning format is an easy way to ensure optimal performance. This forgoes calibration, external hardware or inputs. Estimates of up to 49 percent of the energy can be recovered through the use of flash steam routed to heat exchangers or the deaerator to preheat boiler makeup water or support the deaeration process, respectively. In addition, better level control technology at the boiler side eliminates energy losses resulting from unnecessary blowdown to prevent carryover conditions.
Remote Accessibility – Industrial processes often span across intricate and complex facilities. IIoT radar sensors grant operators and engineers the ability to access data remotely eliminating the need for physical proximity to the sensor. This functionality simplifies troubleshooting, reduces response times to irregularities and minimizes periods of inactivity. Predictive Maintenance – One of the advantages of IIoT-enabled radar sensors is their capability to anticipate maintenance requirements. By analyzing data patterns these sensors can forecast when maintenance or calibration will be necessary, allowing for intervention before problems escalate. This predictive maintenance feature significantly improves equipment reliability and lifespan.
As one of the most professional magnetic level indicators manufacturers in China,Guangdong Kaidi Energy Technology Co., Ltd. provides customized solutions for a range of industrial automation process applications,such as mechanical float level indicator.We specialized in radar level gauge, fork type level switch,etc. These were implemented successfully, and KAIDI magnetic level gauge manufacturers products,such as radar level meter, magnetic level indicators, can be used in many different industries such as food & beverage, water, energy, pharmaceutical etc. Discover more information at https://www.kaidi86.com/. The Magnetic Level Gauge all use vacuum tube technology, with a lifespan of 3-5 years, and protection grade is up to IP68, not easy to fade.
The interference comes not only from the outside, but also from the inside of the radar level gauge, such as interference caused by wires, inductance and capacitance between the power transformer and electronic components. In addition, the internal components can also generate noise interference. Today, most radar level gauges have also begun to be improved, using high-frequency microwave technology, which greatly improves the performance of the level gauge and reduces interference.
Rod antenna: generally used in strong corrosive environments, with weak anti-interference ability and small range; Flare antenna: stronger anti-interference ability, suitable for more complex environments. The larger the bell mouth, the more concentrated the energy, and the larger the measuring range; Parabolic antenna: the focusing effect is stronger than that of the bell mouth, the anti-interference ability is the strongest, and the range is the largest.
In addition, some silos in cement plants are very high, such as homogenizing silos of 50cm. It takes time and energy to board high silos to debug radar, so it is recommended to choose HART handheld operators that can be debugged remotely in the central control room. In the central control room, the range and other basic parameters can be set, and the radar echo waveform can be observed, and the waveform can be used for remote diagnosis and debugging, greatly reducing the on-site work intensity of the staff, to avoid the risk of climbing operation. The smart radar level gauge commonly used at present also has a function similar to “driving recorder”, that is, when the material surface mutation occurs on the scene, it can capture the radar echo waveform at that time, which is very useful for debugging the silo under complex conditions.
Under many operating conditions, ultrasonic level meter and radar level meter are commonly used. Some users are very entangled in the choice of these two level meter and do not know how to choose. Today, let’s talk about the principles and selection principles of these two types of level meter . Principle and selection principle of ultrasonic level meter. Working principle: The ultrasonic pulse probe emits a beam of ultrasonic pulses to the measured medium, and the sound wave is reflected by the liquid surface. The distance between the liquid levels is measured by measuring the time difference between the emission and reflection of the sound waves. Since the ultrasonic level gauge is not a liquid, it can be used to measure corrosive, non-volatile and non-foaming places.
Product features: The gas display is red and the liquid display is green, the luminous display is clear, the observation is large, and the visual distance is long. The liquid level sensor can be clearly displayed by red and green light column, which is suitable for application in dark places and more eye-catching at night. The body is made of stainless steel, the level meter display device does not contact the medium in the container, and there is no leakage. Suitable for first, second and third class containers, suitable for containers containing flammable, toxic and corrosive media.